The NI cRIO-9047 is an 8-slot CompactRIO controller built for industrial applications demanding high performance across extended temperature ranges. It combines a quad-core Intel Atom E3940 processor running at 1.6 GHz (1.8 GHz burst) with a Xilinx Kintex-7 70T FPGA for deterministic control, data acquisition, and embedded monitoring. The controller runs NI Linux Real-Time and supports LabVIEW, LabVIEW Real-Time Module, and LabVIEW FPGA Module for custom application development and FPGA coprocessing.
Technical Specifications
Processor & Memory
• Intel Atom E3940 quad-core CPU: 1.6 GHz base, 1.8 GHz burst
• 2 MB on-die L2 cache
• 4 GB DRAM, 4 GB nonvolatile storage
• Xilinx Kintex-7 70T FPGA with 4,860 kbits block RAM
Connectivity
• 2x Gigabit Ethernet (IEEE 802.3): 10/100/1000 Mb/s auto-negotiated, 100 m/segment maximum
• RS-232 serial: up to 115,200 b/s
• RS-485 serial: up to 230,400 b/s, 1.2 km reach without surge limitation
• 3x USB ports: one Type-A host (480 Mb/s USB 2.0), two Type-C hosts/dual-role (5 Gb/s USB 3.1)
• SD card slot (standard and high-speed cards prohibited)
Operating Environment
• Temperature: -40 °C to 70 °C operating, -40 °C to 85 °C storage
• Humidity: 10–90% RH operating (noncondensing), 5–95% RH storage (noncondensing)
• IP20 ingress protection
• Dimensions: 328.8 mm × 88.1 mm × 121.2 mm (12.94 × 3.47 × 4.77 inches)
• Weight: 4 lbs, 1 oz
– Key Features
• Eight C Series module slots for scalable I/O expansion
• Time-Sensitive Networking (TSN) for synchronized timing in distributed systems
• NI-DAQmx driver and FPGA Module support for advanced signal processing
• Real-Time, Real-Time Scan, and FPGA programming modes for C Series modules
• C/C++ development tools available for NI Linux Real-Time
– Typical Applications
Deterministic embedded control, high-speed data acquisition, distributed measurement systems, industrial automation with thermal extremes.
– Compatibility & Integration
Requires LabVIEW 2017 or later, LabVIEW Real-Time Module, and LabVIEW FPGA Module (2017+) for full functionality. CompactRIO Device Drivers (December 2017+) and NI-DAQmx 17.6 or later necessary for operation.