Opto-22 G4ODC5R Digital Dry Contact DC Output Module

$0.00

Offer available until December 31, 2027

Opto-22 Industrial Controllers & PLCs. Voltage: 100 VDC / 130 VAC, Current: 0.5 A, Current: 14 mA.

In stock

SKU: G4ODC5R Category: Brand:

The Opto 22 G4ODC5R is a digital dry contact DC output module engineered for industrial automation systems within the G4 I/O family. It employs a Form A, SPST-NO mechanical reed relay to switch low-voltage DC resistive loads while maintaining 4000 V transient optical isolation between field devices and control logic. The module operates on 5 VDC logic and includes a built-in status LED.

Technical Specifications

• Contact Form: Form A, SPST-NO mechanical reed relay
• Logic Level: 5 VDC
• Output Type: Dry contact
• Maximum Switching Voltage: 100 VDC / 130 VAC
• Maximum Switching Current: 0.5 A
• Contact Rating: 10 VA
• Maximum Contact Resistance: 200 mΩ
• Turn-On Time: 500 µs
• Turn-Off Time: 500 µs
• Contact Bounce: <500 µs
• Mechanical Life: 5 million cycles
• Coil Current: 14 mA
• Optical Isolation: 4000 V transient
• Operating Temperature: -30°C to 70°C
• Dimensions: 1.92 in L × 0.16 in D
• Agency Approvals: CE, CSA, UKCA
• RoHS Compliant: Yes – Key Features • Optical isolation protects control circuits from field-side transients
• Low coil current draw of 14 mA minimizes controller load
• Fast switching response with 500 µs turn-on and turn-off times and <500 µs contact bounce
• Extended mechanical life rated at 5 million cycles for high-reliability applications
• Built-in LED status indicator for field diagnostics – Typical Applications Analog signal multiplexing, communication line switching, and DC load control in industrial control systems where galvanic isolation is required. – Compatibility & Integration Designed for Opto 22 G4 I/O family integration. Compatible with Totem Pole or Tri-State output modules. Not compatible with G4PB4R mounting racks. Load must be purely resistive; inductive and capacitive loads are not recommended due to inrush current constraints. Steady-state and momentary inrush must not exceed 10 VA.

MPN

G4ODC5R

Voltage / Current Range

5 VDC logic; 100 VDC / 130 VAC output; 0.5 A maximum; 10 VA contact rating

Brand Name

Opto-22