The Remcor CH550 is a compact industrial water chiller engineered for precise temperature control in laboratory and manufacturing environments requiring consistent cooling performance. The unit delivers 6000 BTU/h cooling capacity through a 0.5 HP compressor operating on single-phase 115 V, 60 Hz power. Temperature stability is maintained within ±1°F across a 40°F to 100°F operating range via a hot gas by-pass system. The air-cooled refrigeration circuit uses R134a refrigerant and is housed in a sheet metal enclosure with perforated panels for efficient air circulation.
Technical Specifications
• Cooling Capacity: 6000 BTU/h (0.5 Ton nominal)
• Compressor: 0.5 HP
• Temperature Range: 40°F to 100°F (4.4°C to 37.8°C)
• Temperature Stability: ±1°F
• Refrigerant: R134a, 22 oz. (1.375 lbs.)
• Condenser: Air-cooled
• Reservoir Capacity: 2 gallons
• Pump Output: 2 GPM
• Connections: 3/4 inch FPT inlet/outlet
• Voltage: 115 V, 1 phase, 60 Hz
• Full Load Amps: 15.75 A, 13 A
• Dimensions: 24″ L × 15″ W × 28.5″ H × 16.75″ D
• Weight: 160 lbs.
• Operating Ambient: 65°F to 100°F (optimal below 80°F)
• High Pressure Limit: 250 PSIG with reset button
– Key Features
• Digital thermostat and electronic differential thermostat options for precise setpoint control
• Cooling and high/low pressure indicator lights for operational monitoring
• High Pressure Control (HPC) with manual reset prevents over-pressurization
• Optional bypass valve allows flow adjustment and internal recirculation on positive displacement pump units
• Integrated 2-gallon reservoir and 2 GPM circulation pump
• No. 20 mesh inlet strainer prevents particulate contamination (monthly cleaning recommended)
– Typical Applications
Mold cooling, analytical instrumentation, process water circulation, closed-loop thermal management, and tank cooling requiring flow rates up to 2 GPM and modest cooling loads.
– Compatibility & Integration
Electrical installation must conform to the National Electric Code and local codes. Install indoors with minimum 6 inches clearance on all sides. Avoid ambient temperatures exceeding 110°F and locations subject to external heat loads. Flexible hoses and fittings are recommended for inlet/outlet connections.