The MTA / ICS TAE EVO 015 is an air-cooled process chiller delivering 8.5 kW cooling capacity (7.3 kW CWLT at 25°C ambient) for industrial temperature control applications. Built with hermetic scroll compressors and R410A refrigerant, it combines a high-efficiency finned-coil evaporator immersed in the water tank with an oversized air-cooled condenser to handle variable thermal loads and contaminated process fluids. The unit operates across inlet temperatures to +35 °C and outlet temperatures as low as -10 °C, with precise ±0.5 °C control available in close-tolerance versions. Electrical configurations span 400V/3/50 Hz and 460V/3/60 Hz, with IP44 protection enabling outdoor deployment. An internal pump (3 bar standard, 5 bar optional) supports both atmospheric and pressurized hydraulic circuits to 6 barg. The parametric iCHiLL 208CX microprocessor controller integrates outlet temperature regulation, alarms, and external interface capability alongside comprehensive safety circuits including phase monitoring, pressure switches, and antifreeze sensors.
Technical Specifications
• Cooling Capacity: 8.5 kW (7.3 kW CWLT @ 25°C ambient)
• Refrigerant: R410A
• Compressors: Hermetic scroll compressors
• Evaporator: High-efficiency finned coil, copper tubes with aluminum fins, tank-immersed configuration
• Condenser: Air-cooled, oversized design with copper tubes and aluminum fins
• Fans: Axial design with galvanized steel or die-cast aluminum/plastic crescent blades
• Power Supply: 400V/3/50 Hz and 460V/3/60 Hz (dual frequency available)
• Electrical Protection: IP44 (models 015–020); IP54 (models 031–602)
• Controller: Parametric microprocessor (iCHiLL 208CX)
• Pump: Internal, 3 bar standard (5 bar option available)
• Hydraulic Circuit: Atmospheric and pressurized (up to 6 barg / 87 psig)
• Dimensions: 560 × 1320 × 790 mm (W × D × H)
• Weight: 127 kg
– Key Features
• Oversized water storage tank accommodates load imbalances and maintains steady control under variable thermal loads
• Close-control versions deliver ±0.5 °C hysteresis regulation
• Immersed evaporator design permits high flow rates with minimal pressure drops
• Comprehensive safety: phase monitor, pressure switches, antifreeze sensors, crankcase heaters, internal hydraulic bypass, and automatic circuit breakers for compressor, pump, and fans
– Operating Limits
• Water inlet temperature (Tw in): Maximum +35 °C (+95 °F)
• Water outlet temperature (Tw out): Minimum -10 °C (+14 °F)
• Ambient temperature (Tamb): Maximum +46 °C (+114.8 °F); Minimum -5 °C (+23 °F)
– Typical Applications
• Plastics manufacturing process cooling
• PET bottle recycling operations
• General industrial process plant cooling
• Data and power transmission temperature control