The Thermo Neslab HX-540 is a three-phase recirculating chiller engineered for precise temperature control in laboratory and industrial cooling applications. This water-cooled system delivers stable temperature maintenance across variable heat loads, making it suitable for laser cooling, analytical instrumentation, semiconductor manufacturing, and reaction vessel temperature management. A microprocessor controller maintains operating temperature stability typically within a few tenths of a degree Celsius, while the stainless steel reservoir and continuous-duty design ensure reliable long-term operation in demanding environments.
Technical Specifications
Thermal Performance
• Temperature range: −15°C to +90°C (configuration-dependent)
• Temperature stability: Within a few tenths of a degree Celsius
• Cooling capacity: Up to 24,000 W
• Cooling capacity derating: 1% per 1°C above +30°C facility water temperature
• Heat load tracking: Maintains set temperature virtually independent of changing heat loads
Refrigeration & Fluid
• Refrigerant: R404A
• Cooling fluid: Distilled/deionized water (1–3 MΩ/cm² resistivity with DI water package) or filtered water; ethylene glycol for temperatures below +8°C
• Fluid specific heat: 0.6 BTU/lb°F
• Fluid specific gravity: 0.5
• Reservoir: Stainless steel, 8.0 gallons
Pump & Flow
• Pumping capacity: Variable by pump type and backpressure; example 7.6 LPM @ 2.8 bar
• Available pump types: Positive Displacement (PD), Centrifugal (CP), Turbine (TU)
Electrical
• Configuration: Three-phase
• Voltage tolerance: ±10% of specified voltage
• Example supply: 208 V, 50 Hz
– Key Features
• Microprocessor-based temperature controller with digital display
• Water-cooled refrigeration for high-capacity heat removal
• Stainless steel reservoir for corrosion resistance
• Multiple pump options to match application requirements
• Rated for continuous operation in critical cooling applications
– Typical Applications
• Laser systems cooling
• Analytical instrumentation temperature control
• Semiconductor manufacturing processes
• Reaction vessel and process fluid temperature management
– Compatibility & Integration
The HX-540 accommodates standard cooling fluids and integrates with multiple pump configurations. Facility water temperature and ambient conditions influence cooling capacity and should be evaluated during system selection.