The Sorensen DHP50-40 is a programmable DC power supply delivering 2.0 kW across 0–50 VDC and 0–40 A in a single-output configuration. Designed for research, development, and test environments, this unit operates in Constant Voltage, Constant Current, and Constant Power modes with ±0.1% voltage regulation and ±0.2% current regulation. Output stability reaches ±0.05% after 8 hours warm-up, with transient response of 2 ms to steady state for 30% load steps. The DHP50-40 accepts 190–253 VAC, 47–63 Hz single or three-phase input and achieves minimum 80% efficiency at full load.
Technical Specifications
• Output Power: 2.0 kW
• Voltage Range: 0–50 VDC
• Current Range: 0–40 A
• Voltage Regulation: ±0.1% of maximum output voltage
• Current Regulation: ±0.2% of maximum output current
• Stability: ±0.05% of set point after 8 hours warm-up
• Temperature Coefficient—Voltage: 0.02%/°C of rated output voltage
• Temperature Coefficient—Current: 0.03%/°C of rated output current
• Transient Response: 2 ms to steady state for 30% load step
• Input Voltage: 190–253 VAC
• Input Frequency: 47–63 Hz
• Minimum Power Factor: 0.72
• Minimum Efficiency: 80% at full load
– Key Features
• Three operational modes: Constant Voltage, Constant Current, Constant Power
• Auto-step sequencing with up to 9 steps, each configurable from 1 second to 99,999 seconds (27.75 hours maximum)
• Remote sensing terminals to monitor voltage at load point with maximum 3% line drop per line or 2 V maximum
• Output on/off control via contact closure, TTL, or CMOS logic
• Front-panel controls with voltage and current adjustment via up/down arrows
• Overvoltage Protection (OVP) limit control
• Digital displays showing power rating, output power, voltage, current, set points, limits, AC input voltage, and inlet temperature
– Interfaces and Integration
• Standard analog programming
• IEEE-488.2 (M9D Option)
• RS-232
• Isolated analog input control options
• Output voltage and current monitoring capability
• Summary fault status reporting
• Front-panel lockout function
– Electrical Input
Single-phase or optional three-phase 190–253 VAC, 47–63 Hz input with 0.72 minimum power factor.