The Sorensen DHP50-60 is a programmable DC power supply delivering 3000 W of output power in a single chassis. It operates across 0–50 VDC at 0–60 A, supporting constant voltage, constant current, and constant power modes for laboratory, R&D, and manufacturing test environments. The unit combines low output ripple (10 mV typical), fast transient response (2 ms to steady state for 30% load step), and tight line and load regulation (0.1% voltage, 0.5% current) to meet precision power delivery requirements. Multi-step sequencing capabilities—up to 9 steps per sequence, 99,999 seconds per step—enable complex automated test protocols. Voltage, current, and duration are independently programmable. The front panel keypad provides direct control with nine nonvolatile memory slots, while soft calibration adjusts output without chassis disassembly. Remote sense terminals compensate for line drop up to 3% of rated voltage. Temperature stability is ±0.05% after 8-hour warm-up, with temperature coefficients of 0.02%/°C (voltage) and 0.03%/°C (current). Input is 200–240 VAC, 3-phase with 0.72 minimum power factor.
Technical Specifications
• Output Power: 3000 W
• Output Voltage: 0–50 VDC
• Output Current: 0–60 A
• Operating Modes: Constant Voltage, Constant Current, Constant Power
• Output Ripple (RMS): 10 mV typical
• Line Regulation: 0.1% voltage, 0.5% current
• Load Regulation: 0.1% voltage, 0.5% current
• Stability: ±0.05% of set point (post 8-hour warm-up)
• Temperature Coefficient: 0.02%/°C voltage, 0.03%/°C current
• Transient Response: 2 ms to steady state (within 2% Vmax) for 30% load step
• Input: 200–240 VAC, 3-phase; Power Factor ≥0.72
– Key Features
• Auto-sequencing: 9 programmable steps, up to 99,999 seconds per step
• Remote sense with up to 3% voltage drop compensation per line
• Isolated analog programming option for ground isolation
• Remote On/Off control (6–120 VDC, 12–240 VAC, TTL/CMOS compatible)
• Output voltage and current monitor (0–10 V)
• OVP limit adjustment and summary fault status monitoring
• Nine front-panel memory slots for parameter storage
– Interfaces & Control
• Standard: Analog control
• Optional: IEEE-488.2 + RS-232, IEEE-488.2 + isolated analog input, or RS-232 standalone
• Remote monitoring and control via rear panel connectors
– Typical Applications
Automated test systems, power conversion validation, component stress testing, and multi-stage charging or discharge protocols requiring programmable sequencing.