The TDK-Lambda / Nemic-Lambda GEN 30-25-IEEE is a 750W programmable DC power supply from the Genesys series, purpose-built for OEM, industrial, and laboratory environments. It delivers adjustable output from 0 to 30 VDC at 0 to 25A with universal AC input (85 to 265 VAC, single-phase, 47 to 63 Hz) and active power factor correction rated at 0.99 typical. The unit combines constant voltage/constant current auto-crossover with intelligent protection—adjustable OVP, UVL, OCP, and OTP—ensuring safe operation across demanding applications.
Technical Specifications
• Output Power: 750W at 30 VDC, 25A
• Voltage Output: 0 to 30 VDC with voltage ripple noise of 0.008 Vrms (5 Hz to 1 MHz)
• Current Output: 0 to 25A with current ripple noise of 0.063 Arms (5 Hz to 1 MHz)
• Input Voltage: 85 to 265 VAC continuous, single-phase
• Input Frequency: 47 to 63 Hz
• Power Factor: 0.99 typical @ 100 VAC / 200 VAC
• Efficiency: 85% to 86% typical
• Interfaces (Standard): RS-232, RS-485
• Interfaces (Optional): LAN (LXI compliant), GPIB, electrically isolated analog interface, USB
• Package: 1U rack-mount or benchtop configuration
• Dimensions: Multiple variants available—GEN30-25/LN at 432.8 × 43.6 × 422.8 mm; GEN30-25 at 422.8 × 43.6 × 432.8 mm; GENH30-25 at 214 × 43.6 × 437.5 mm
• Weight: 9.5 kg (GEN30-25/LN), 7.0 kg typical (GEN30-25), 4.5 kg typical (GENH30-25)
– Key Features
• Four-digit LED displays for real-time voltage and current monitoring
• Remote analog programming selectable between 0–5V, 0–10V, or 4–20mA control current via rear-panel DIP switches
• Last Setting Memory function retains user settings without battery backup
• Safe Re-Start capability—user selectable to resume prior settings or initialize to zero output
• Front panel encoders for coarse/fine voltage and current adjustment
• Software-controllable or hardware-based front panel lockout
• Local/Remote Digital selection mode
– Typical Applications
OEM system integration, industrial test benches, laboratory power sourcing, prototype validation, and equipment commissioning requiring precision DC output with digital control and diagnostics.
– Compatibility & Integration
RS-232 and RS-485 interfaces are standard. Optional LXI-compliant LAN, GPIB, and isolated analog interfaces enable seamless integration into automated test systems, SCADA environments, and laboratory infrastructure. Output programming accepts 0–5V, 0–10V, or 4–20mA command signals.