The GE / Bently Nevada 1701/10 is a 24 Vdc power supply module engineered for the FieldMonitor system. It converts input power across a wide industrial range and delivers stable logic and transducer voltages to all FieldMonitor modules. Designed for hazardous area deployment, this unit integrates directly into 1701/05 or 1701/06 terminal bases and operates reliably across demanding temperature and humidity environments.
## Technical Specifications
**Electrical Performance**
• Input voltage range: +18 Vdc to +36 Vdc
• Nominal inrush current: 30 A peak
• Fusing: 250 V, 3 A, SB
• Isolation voltage: 850 Vdc primary to chassis (1 minute)
• Overvoltage protection: No damage to 50 Vdc
• Input conductor size: 14 to 26 AWG
**Physical Dimensions**
• Size: 105 mm × 150 mm × 56 mm (4.1 in × 5.9 in × 2.2 in)
• Weight: 0.57 kg (1.25 lb)
• Form factor: Plug-in module for designated power supply slot
**Environmental & Operating Limits**
• Operating temperature: −20°C to +70°C (−4°F to +158°F)
• Storage temperature: −40°C to +85°C (−40°F to +185°F)
• Operating humidity: 5% to 95% non-condensing RH
• Storage humidity: 5% to 95% non-condensing RH
## Key Features
• Accepts industrial-range DC input with integrated surge protection
• Isolated power architecture for safety-critical monitoring applications
• Compact, slot-mounted design minimizes footprint within terminal bases
• Certified for North American, European, and Brazilian hazardous areas
• SB-type fusing for coordinated circuit protection
## Typical Applications
• Machinery condition monitoring in Class I, Division 2 locations
• Hazardous gas atmosphere installations (Groups A, B, C, D)
• Industrial vibration and temperature monitoring networks
• On-site FieldMonitor system expansion and field service
## Compatibility & Integration
This power supply mates exclusively with Bently Nevada 1701/05 and 1701/06 FieldMonitor Terminal Bases. It occupies a dedicated power module slot and supplies all required voltages to subordinate monitoring cards. Spare fuses (01700025) are stocked for field replacement.